The ECHO LEVEL HUNTER II is an advanced, low cost, ultrasonic level measurement system that utilizes the latest state-of-the-art technology to provide reliable measurement and control. It can accurately measure level and volume (pre-configured tank shapes) and perform alarm and fixed pump control for up to 4 pumps. Standard features include: 1 4-20mA output, 4 SPDT Relays, LED's for alarm/pump status and Quick Setup menu-driven programming. It also comes standard with a RS-232 serial communication port and optional RS-485.
The six buttons allow for easy programming using a quick set up method. No manual needed. Echo Process Instrumentation has eliminated the need for complex parameter programming. It uses a simple question and answer sequence which allows the Level Hunter II to be programmed in minutes. Housed in a rugged NEMA 4X enclosure with easy access to the wiring terminals, the Level Hunter II is the ideal instrument for non-contact ultrasonic level measurement and alarm/pump control.
Big in functionality and small on price, the Level Hunter II is perfect for the toughest applications. We offer a standard 60 day Performance Guarantee and 1 year warranty. We will prove our technology and high quality product is the best in the market and completely risk free to the customer. A totally flexible solution!
-Level Measurement up to 50 ft (15 m)
-Alarm/Pump Control
-Tank farm monitoring
-Overflow and pump dry protection
-Sluce gate control
-Proximity detection
A complete system comprises of 1 Level Hunter II and 1 XDS Transducer to measure and control your level or pumps.
Technical Specifications: Level Hunter II
TECHNOLOGY/ OPERATION
Measuring Principle Ultrasonic Level Measurement
PERFORMANCE
Measuring Range Transducer Dependent, 0 - 50 ft (0 - 15 m)
XDS Transducer Models: XDS 08 = 0 - 8m (26ft) range, 0.35m (1.1ft blanking distance)
XDS 12 = 0 - 12m (40ft)
range, 0.5m (1.6ft blanking distance)
XDS 15 = 0 - 15m (50ft)
range, 0.5m (1.6ft blanking distance)
Transducer Cable Extensions Use 2-conductor/ shielded 16/18 AWG
Accuracy +/- 0.25% of measured range or 6mm (whichever is greater)
Echo Processing ECHO LOGIC Sophisticated algorithms using Advanced DSP Processing
Power Supply 100 ... 240VAC 50/60 Hz, Optional 24 VDC
Power Consumption Typically <5W, 11W maximum if relays energized
Channels 1
OUTPUTS
Analog 1 4-20mA output, 600 ohm max.
Relay 4 Form "C" SPDT Relays, 5A @ 250 VAC
Relay Function High, HiHi, Low, LoLo Alarms
Fixed Pump Control
Volume High or Low Alarm
Communication Standard RS 232, Optional: RS 485
PROGRAMMING
User-interface 6 button integral keypad with menu-driven programming
Display 2 lines, 40 characters LCD
Relay Indication LED Indication for Relay Status
Programming Security Password protected
Data Integrity Non-volatile RAM
ENVIRONMENT
Temperature Range (Electronics) -4°F to +140°F (-20°C to +60°C)
Temperature Range (Transducer) -40°F to +158°F (-40°C to +70°C)
Temperature Compensation Integral Temperature Sensor with Automatic Compensation
Outdoor Rating (Electronics) NEMA 4X (IP 65), UV Protected Clear Lid
DESIGN
Dimensions 7.3H x 9.4W x 4.2W inch (185 x 240 x 107 mm)
Cable Entry 11 available for Wall Mount Enclosure
Mounting 2 fixed holes & 1 hanging hole
Enclosure Material Plastic, ABS, Polycarbonate (transparent front lid)
Weight Approximate 3 lbs (1.4 kg)
WARRANTY
Product Warranty 1 year
TRANSDUCER
XDS 08 Dimensions 2.6" dia x 5.1" ht (67mm x 131mm)
Explosion Proof EEX d II T6
XDS 12 Dimensions
3.3" dia x 6.0" ht (84mm x 152mm)
Explosion Proof EEX d II
T6
XDS 15 Dimensions
4.5" dia x 6.8" ht (115mm x 173mm)
Explosion Proof EEX d II
T6